Overview
HD 60364-4-46:2016 (published as SIST HD 60364-4-46:2017 in Slovenia) is a Harmonization Document (HD) developed by the European Committee for Electrotechnical Standardization (CENELEC). This standard specifies essential requirements for isolation and switching in low-voltage electrical installations to ensure the safety of people, livestock, and property.
This document focuses on:
- Non-automatic local and remote isolation and switching to prevent or remove dangers linked to electrical installations or powered equipment
- Switching for the functional control of electrical circuits or equipment
HD 60364-4-46:2016 forms part of the widely used IEC 60364/HD 60364 series for low-voltage electrical installations, targeting designers, installers, inspectors, and maintenance personnel.
Key Topics
1. Isolation
- Every electrical installation must include means for isolation from each supply source.
- Each circuit should have provisions for isolation of all live conductors, unless specific exemptions apply (such as PEN conductors in TN-C systems).
- Measures should be in place to prevent unwanted or unintentional energization, including discharge means for residual energy.
2. Functional Switching (Control)
- Functional switching must be available for each part of a circuit requiring independent control.
- Devices do not always need to switch all live conductors; however, specific restrictions apply, especially concerning neutral conductors.
- Functional switches may be used for simultaneous control of multiple current-using devices if required.
3. Motor Control
- Motor circuits must prevent unintentional or hazardous restarting after loss of supply.
- Earth faults or phase reversal should be managed to prevent dangerous operation or equipment damage.
4. Switching Off for Mechanical Maintenance
- Means must be provided for switching off equipment where mechanical maintenance poses a risk of physical injury. This should disconnect all live conductors and prevent unintentional reactivation unless continuously supervised.
5. Emergency Switching Off